BUILD THE (IM)POSSIBLE: Join The International Contest and Win the Challenge!

HIGH FIRE-RESISTANT SEALING POLYURETHANE FOAM

FIRE FOAM

New

FIRE FOAM is the only ETA tested and certified sealing foam for fire protection and sealing of linear joints and cracks.

Tested in the event of fire to provide protection against combustion fumes and heat for up to 240 minutes.

FIRE FOAM, the EI240 fire-certified high-performance foam sealant

Its uniform cell structure, dimensional stability and mechanical properties make the foam ideal for insulating, sealing and filling in all cases of high fire protection requirements.

Documents

Technical data sheets
Declaration of performance (DOP)
Fire test report

FIRE FOAM

CODE content
[ml]
yield
[l]
contenuto
[US fl oz]
resa
[US gal]
description version pcs.
FIREFOAM 750 42 25.36 11.1 ALUMINIUM CARTRIDGE GUN 12

Technical Data
ETA
EN 13501-1 B-s1,d0
EN 13501-5 EI240
DIN 4102-1 B1
GLOVESINCLUDED

Property Standard Tested Values USC Conversion
Post expansion EN 17333-2 90 / 120 % -
Yield - 42 dm3 0 ft3
Tempo di formazione della pellicola 23°C / 50% RH (1) - 10 / minutes -
Tempo di taglio 23°C / 50% RH (1) - 40 / minutes -
Tempo necessario per completo indurimento 23°C / 50% RH (1) - 1440 minutes -
Application temperature (ambient, cartridge and support) (2) - 10 / 30 °C 50 / 86 °F
Dimensional stability EN 1107-2 ≤ 3 % -
Reaction to fire EN 13501-1 class B-s1,d0 -
Reaction to fire DIN 4102-1 class B1 -
Classe di resistenza al fuoco su giunto in calcestruzzo * (3) en 1366-4 EI240 -
Classe di resistenza al fuoco su giunto in CLT * (3) en 1366-4 EI90 -
Emicode procedura di prova GEV EC1 plus -
French VOC classification ISO 16000 A+ -
Transport temperature - -20 / 30 °C -4 / 86 °F
Storage temperature - 5 / 30 °C 41 / 86 °F
1. The data expressed may vary depending on the thickness of the product applied and the specific installation conditions: temperature, humidity, ventilation, absorbency of the substrate.
2.
3.