HOME
AIRTIGHTNESS AND WATERPROOFING
TAPES AND SEALANTS
SEALANTS, FOAMS AND LIQUID MEMBRANES
FIRE SEALING ACRYLIC
New
FIRE SEALING ACRYLIC
HIGH FIRE-RESISTANT ACRYLIC SEALANT
FIRE SEALING ACRYLIC is a highly fire-resistant acrylic sealant for use in applications subject to fire regulations up to EI 240. The product can be overpainted with the most common water-based paints and varnishes.
FIRE SEALING ACRYLIC, the high fire-resistant acrylic sealant
Description
FIRE SEALING ACRYLIC acrylic sealant is versatile: it ensures good workability, adheres also to moist substrates, does not drip and is easily smoothed. EMICODE EC1 PLUS certified by GEV in terms of very low emissions of Volatile Organic Compounds.
Documents
-
Technical data sheets
- Technical data sheets Croatian
- Technical data sheets Czech
- Technical data sheets English
- Technical data sheets French
- Technical data sheets German
- Technical data sheets Greek
- Technical data sheets Hungarian
- Technical data sheets Italian
- Technical data sheets Polish
- Technical data sheets Portuguese
- Technical data sheets Romanian
- Technical data sheets Russian
- Technical data sheets Slovene
- Technical data sheets Spanish
-
Fire test report
-
EMICODE Certificate
Technical Data
| Property | Standard | Tested Values | USC Conversion |
|---|---|---|---|
| Composition | - | based on acrylic polymers in water dispersion | - |
| Classification (1 ) | EN 15651-1 | F-INT | - |
| Density | - | 1,7 kg/L | 14.19 lb/gal |
| Yield for 10x10 mm joint | - | 5,5 m | 18.04 ft |
| Surface cross-linking time 20 °C / 50% RH (2 ) | - | 30 minutes | - |
| Time required for complete hardening 23 °C / 50% RH (2 ) | - | 10 days | - |
| Elongation | DIN 53504 | 700 % | - |
| Reaction to fire | EN 13501-1 | class B-s1,d0 | - |
| Fire resistance rating on concrete joint* (3 ) | en 1366-4 | EI240 | - |
| French VOC classification | ISO 16000 | A+ | - |
| Emicode | procedura di prova GEV | EC1 plus | - |
| Storage temperature | - | 5 / 35 °C | 41 / 95 °F |
| Fire resistance rating on CLT joint* | en 1366-4 | EI90 | - |
| Application temperature (4 ) | - | 5 / 30 °C | 41 / 86 °F |
1.
2. The data expressed may vary depending on the thickness of the product applied and the specific installation conditions: temperature, humidity, ventilation, absorbency of the substrate.
3. For full details and tested configurations, please refer to the manual or contact our technical department.
4.